| Device | Type | Watts | Qty | Connector | Circuit | Action |
|---|
*Calculations are for continuous loads > 3 hours. Minimum gen size ensures the running load does not exceed 80% of the generator's prime power rating. Always verify with specific equipment tolerances.
*Bars turn Yellow at 80% (Continuous Load Limit) and Red at 100% Breaker Capacity.
| Gauge | Ampacity | Max Continuous (80%) |
|---|---|---|
| 18 AWG | 10 A | 8 A |
| 16 AWG | 13 A | 10 A |
| 14 AWG | 18 A | 14 A |
| 12 AWG | 25 A | 20 A |
| 10 AWG | 30 A | 24 A |
| 8 AWG | 40 A | 32 A |
| 6 AWG | 55 A | 44 A |
| 4 AWG | 70 A | 56 A |
| 2 AWG | 95 A | 76 A |
| 1/0 AWG | 150 A | 120 A |
| 2/0 AWG | 225 A | 180 A |
| 4/0 AWG | 405 A | 324 A |
*Ampacity is a strict thermal limit based on wire thickness (NEC Table 400.5), independent of length. For runs over 50 feet, always check the Voltage Drop Calculator to ensure adequate voltage reaches your equipment.